Summary
T30 series of outdoor temperature and humidity sensors can be used in various intelligent buildings, HVAC systems, such as airports, stations, subway stations, pharmaceutical factories, museums, intelligent buildings and gymnasiums.The product adopts a high-performance built-in linear processor and has a variety of output signals. The probe uses PC material and a protective head with polymer material. It can guarantee the measurement accuracy and prolong the service life of the sensor in the humid and dusty environment. It can meet the measurement requirements of different measuring environments and various high precision and high stability.
Outdoor temperature and humidity sensor has current, voltage, 485 output, resistance output and other signals optional, 485 serial output, using MODBUS communication protocol.Usually used in HVAC electronic workshop, machine room environment monitoring, power environment monitoring, agricultural environment monitoring, meteorological environment monitoring, biopharmaceutical environment monitoring and other places.
Features
-High Precision Temperature and Humidity Sensor
-Applicable to all kinds of intelligent building environment monitoring, HVAC system
-Advanced circuit design, high measurement accuracy
-Stable performance and good linearity
-Easy to install, cost-effective
-Current/Voltage Output Options
-Sensor factory standard calibration/high humidity calibration
Application
-HVAC
-Electronic factory building
-Environmental Monitoring in Computer Room
-Power Environment Monitoring
-Agricultural Environmental Monitoring
-Meteorological Environmental Monitoring
-Environmental monitoring of biopharmaceuticals
-Airports, subway stations, hotels, museums, gymnasiums, etc.
Parameter
Temperature |
Accuracy: Range: Stabilization Time: Calibration: |
±0.2℃、±0.3℃、±0.5℃、±1℃ 0~50℃、0~80℃、-5~60℃Refer to the Selection Table 2-5mins Standard calibration |
Humidity |
Accuracy: Range: Stabilization time: Calibration: |
±2%RH、±3%RH、±5%RH 0~100%RH 2-5mins Standard calibration/high humidity calibration |
Output Parameter |
Signal output: |
4~20mA RL<400 ohm Refer to the Selection Table for details |
485 Parameter |
Signal type: RS485 type: Connect: Address: Protocol: Data format: Baud rate: |
RS485 Serial Port Output Multipoint, Half Duplex 2Wire system, maximum communication distance 1200 meters, terminal direct connection 1-254 Through the switch/software settings, the broadcast address is: 0, and the default address is: 1 MODBUS 1Start bits, 8 data bits, no parity, 2 termination bits 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19200 bit/s, 28800 bit/s, 38400 bit/s, through the switch/software settings, the default value is 9600 bit/s. |
Power |
Power supply: |
Current-mode 24VDC±10% Voltage-mode 24VDC/AC±10% RS485 10~28VDC |
Connection mode |
Terminal: Cable Specifications: |
5.0mm spacing, M3 steel screw, 0.2Nm torque, 0.02 ohmic contact resistance 24~18AWG(0.2~1.0mm2),stripping length 6-7mm |
Environmental Science |
Working environment: |
Temperature -20~80℃ Humidity 0~99%RH,no condensation |
Storage environment: |
Temperature -30~80℃ Humidity 0~95%RH,no condensation |
|
Protection level |
Shell: Fire Grade: EMC: |
IP65 Reference IEC 529 – 598/GB 700 – 86/ GB 4208 V-0 Reference UL94 Reference GB/T 13926,EN61000-6-2,EN61000-6-3 |
Material and color |
Shell: Probe: Probe length: Weight: |
ABS (light blue) PC polycarbonate with polymer protective head 60mm Appr. 150 g (total weight) |
Ordering Information
Series |
Type of measurement |
Temperature measurement range |
||||
T30- |
Humidity Temperature and Humidity |
(RH) (TH) |
0~50℃ 0~80℃ -5~60℃ -20~80℃ -40~80℃ -10~50℃ |
(T1) (T2) (T4) (T5) (T6) (T7) |
-20~40℃ -20~60℃ -30~70℃ -40~60℃ Custom |
(T15) (T16) (T20) (T21) (UD) |
Temperature Accuracy |
Humidity measurement range |
Humidity Accuracy |
signal output |
||||
±0.2℃ ±0.3℃ ±0.5℃ ±1℃ |
(B) (C) (D) (E) |
0~100%RH 0~95%RH 10~90%RH 20~80%RH 0~99%RH |
(H1) (H2) (H3) (H4) (H5) |
±2%RH ±3%RH ±5%RH |
(B) (C) (D) |
4~20mA 2-wire 4~20mA 3-wire 0~5VDC 0~10VDC RS485 Output |
(2) (3) (4) (5) (RS) |