TAQU T28 Duct CO2 Sensor Transmitters RS485 0-10VDC 4-20mA MODBUS Infrared Principle TAQU T28 Duct CO2 Sensor Transmitters RS485 0-10VDC 4-20mA MODBUS Infrared Principle TAQU T28 Duct CO2 Sensor Transmitters RS485 0-10VDC 4-20mA MODBUS Infrared Principle TAQU T28 Duct CO2 Sensor Transmitters RS485 0-10VDC 4-20mA MODBUS Infrared Principle TAQU T28 Duct CO2 Sensor Transmitters RS485 0-10VDC 4-20mA MODBUS Infrared Principle

TAQU T28 Duct CO2 Sensor Transmitters RS485 0-10VDC 4-20mA MODBUS Infrared Principle

Price:
 Open price  
Min.Order Quantity:
1 Piece
Supply Ability:
1000 Piece per Day
Port:
Shenzhen
Place of Origin:
China
Payment Terms:
T/T, PayPal
Brand:
TAQU
Products Model:
T28
Share:
  • Products Details

Quick Details

  • Brand Name: TAQU

    Model Number: T28

    Place of Origin: China

Packaging & Delivery

  • Packaging Details: box
  • Delivery Detail: 7-15

Specifications

Summary

T28 series carbon dioxide sensors are applied to the detection and control of CO2 concentration, which can monitor ventilation system, effectively reduce energy consumption and meet the requirements of relevant building ventilation, energy saving and related standards. In garages or motor vehicle maintenance and operation workshops, the start-stop control of ventilation system should be carried out according to the use situation, or the automatic operation control should be carried out according to CO2 concentration.

T28 series carbon dioxide sensors can be used in various intelligent buildings, HVAC systems, such as airports, stations, subway stations, pharmaceutical factories, museums, intelligent buildings and gymnasiums.Infrared principle gas sensor is used in the product. There are many kinds of output signals to choose. Pipeline installation equipped with conductive PC or stainless steel probes can meet the measurement requirements of different measuring environments and various high precision and high stability.

Features

-High Precision Infrared Carbon Dioxide Sensor

-Automatic Protection Function against High Concentration Gas Shock

-Applicable to all kinds of intelligent building environment monitoring, HVAC system

-Advanced circuit design, high measurement accuracy, stable performance

-Lightweight housing, easy to install on site

-Independent chamber structure, fast response

-Calibration of Sensor Exit Standard

 

Aapplication

-Electronic factory building

-Environmental Monitoring in Computer Room

-Power Environment Monitoring

-Agricultural Environmental Monitoring

-Meteorological Environmental Monitoring

-Environmental monitoring of biopharmaceuticals

-Airports, subway stations, hotels, museums, gymnasiums, etc.

 

 

 

Parameter

 

CO2

Sensor Type:

Accuracy:

Range:

Response Time:

Calibration:

Infrared principle

±30PPM+3%reading±50PPM+5%reading

0-5000PPM

<10s

Standard calibration

Output Parameter

Signal Output:

 

 

Relay:

420mA       RL<400 ohm

010VDC      RL>10k ohm

Relay output can be selected by keys or jumpers

1 x SPST, 1A/30VDC

485 Parameter

Signal Type:

RS485 Type:

Connect:

Address:

Protocol:

Data Format:

Baud Rate:

RS485 Serial Port Output

Multipoint, Half Duplex

2Wire system, maximum communication distance 1200 meters, terminal direct connection

1-254 Through the switch/software settings, the broadcast address is: 0, and the default address is: 1

MODBUS

1Start bits, 8 data bits, no parity, 2 termination bits

1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19200 bit/s, 28800 bit/s, 38400 bit/s, through the switch/software settings, the default value is 9600 bit/s.

Relay Parameters

Relay:

Threshold:

Backlash:

3A: 12VAC/24VDC

0~ 1999ppm

10 ppm, 20 ppm, 50 ppm, 100 ppm, 150 ppm, 200 ppm

Power

Power Supply:

 

Current-mode 24VDC±10%

Voltage-mode 24VDC/AC±10%

RS485 10-28VDC

Connection Mode

Terminal:

Cable Specifications:

5.0mm spacing, M3 steel screw, 0.2Nm torque, 0.02 ohmic contact resistance

2616 AWG, stripping length 6-7 mm

Environmental Science

Working environment:

Temperature 0...+50

Humidity 0...95%RH, no condensation

Storage environment:

Temperature -20...+70

Humidity 0...95%RH, no condensation

Protection Level

Shell:

Fire Grade:

EMC:

IP65 Reference IEC 529-598/GB 700-86/GB 4208

V-0 Reference UL94

Reference GB/T 13926, EN61000-6-2, EN61000-6-3

Material and Color

Shell:

Probe Material:

Probe Length:

Weight:

ABS (light blue)

PC polycarbonate

150 mm, 200 mm, 250 mm

Appr. 140 g (Total weight)

 

 

Order Options

Series

Range

Accuracy

Signal Output

T28-

02000PPM

05000PPM

02%

05%

 

(P1)

(P2)

(P3)

(P4)

 

±30PPM+3%reading

±50PPM+5%reading

±80PPM+8%reading

(C)

(D)

(E)

 

 

420mA 3-Wire

05VDC

010VDC

Relay Output

RS485

(3)

(4)

(5)

(S)

(RS)

 

Probe Length

150mm

200mm

(T15)

(T20)

 
  • Email to this supplier
  • To :
    Jerry Zhang  |  Taqu Sensor Technologies Co.,Ltd
  • *Subject :
  • Quantity Order:
  • *Message :

  • Your message must be between 20-2000 characters
  •  Please enter your company name:

    Please make sure your company name is entered correctly.

  • * Please enter your email address:

    Please make sure your email address is entered correctly.

  • * Please enter your mobile phone:

    Please make sure your mobile phone is entered correctly.

Verified Supplier - Taqu Sensor Technologies Co.,Ltd Bussiness Type:  Manufacturer
Scale:  11 - 50 People
Country/Region:  China (Mainland)/Asia
Established: